TeSys GV Motor Circuit Breaker, 3 poles (3P), 25A/690V, for 3-phase motor applications 11kW@400V. It provides a thermal-magnetic protection with a thermal setting range 20-25A, magnetic tripping at 13xIn, high breaking capacity Icu 15kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
| Specification | Value |
|---|---|
| Motor Power | 15 HP |
| Motor Power | 11 kW |
| Breaking Capacity at 415V 50Hz | 15kA |
| IP Degree of Protection | IP20 conforming to IEC 60529 |
| Trip Unit Technology | Thermal-magnetic |
| Number of Poles | 3 Poles |
| Network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
| Tightening Torque | 1.7 N.m - on screw clamp terminal |
| Colour | Dark Grey |
| Ambient Air Temperature for Operation | (-20€¦60 °C) |
We're working on gathering more customer feedback to help you make better decisions.